Part of the Architecture & Design suite · 37 calculators

Exit Width Calculator

The total exit width and the number of exits a space needs for its occupant load — from the width-per-person factor your code uses — with the minimum width of each exit.

Building codes allot egress width per occupant: about 5 mm per person for doors and level routes and 7.

Results update as you type
Results
Total egress width required
1,600 mm
Exits required
Width per exit
Occupants the minimum-width exits alone would serve
Note
Reviewed September 2026. Building physics and geometry are the same everywhere; only the code thresholds move. The IBC is adopted with local amendments; the authority having jurisdiction decides compliance.
No account required · Google Analytics off unless allowedCalculator arithmetic runs in your browserResults update as you type
All calculations run 100% in your browser. The calculator code does not submit your figures to GlobalCalc to obtain a result.
About exit width

How the exit width calculator works

Building codes allot egress width per occupant: about 5 mm per person for doors and level routes and 7.6–8 mm for stairs (the IBC figures), or a flow of 100 persons per 550 mm unit of width in older methods. Multiply the occupants by the factor for the total width, split it across at least two exits above the threshold occupancy (typically 50), and check each exit is at least the minimum clear width, usually 850–900 mm. The occupant load itself comes from the floor area and use.

Formula: total width = occupants × mm per person; exits = max(minimum by occupancy, ceil(total ÷ max width per exit))

Worked examples

InputsTotal egress width requiredNote
320 occupants, 5 mm each1,600 mm1,600 mm across 2 exits of 900 mm
800 occupants on stairs at 7.6 mm6,080 mm6,080 mm across 3 exits of 2,050 mm
A small room of 30150 mm150 mm — one 850 mm exit

Frequently asked questions

Where do the width factors come from?

From measured crowd flow: about 1.3 people per second through a meter of doorway, giving 5 mm per person for a 2.5-minute evacuation in the IBC; stairs are slower, so 7.6 mm. Other codes use similar figures or the 550 mm unit-of-width method.

Why at least two exits?

So that a fire blocking one still leaves a way out. Most codes require two above about 50 occupants, three above 500 and four above 1,000, placed far enough apart that one event cannot block both.

Does the widest exit count fully?

Usually not — codes assume the widest exit may be the blocked one and require the remainder to carry at least half the occupants. Check the local rule when one exit is much wider than the others.

How is the occupant load found?

From the floor area divided by an occupancy factor for the use — 1 m² per person for standing assembly, 2 for dining, 10 for offices. The occupant load calculator in this category gives it.

Where these figures come from

Last checked: September 2026. Formulas are the standard building-science and code relationships; default thresholds are common international values and should be replaced with the ones in your code.